KTA50 for Data Center Continuous (DCC) Rating

Cummins C1760D5, C1875D5, and C2000D5B

Frequency

50, 60 Hz

Rated for kW kVA
Data Center Continuous 1000 - 1286 1250 - 1608

Certification

N/A

Product Availability

Africa Middle East, Asia Pacific, Europe, Latin America

c1400 d5 generator

This Cummins® commercial generator set is a fully integrated power generation system, providing optimum performance, reliability, and versatility for stationary Standby, Prime Power, and Continuous duty applications.

Features & Benefits

Data Center Continuous (DCC) - Applicable for supplying power continuously to a constant or varying electrical load for unlimited hours in a data center application.

Uptime compliant - Meets the requirement of a Tier III and IV data center site by being rated to run for unlimited hours of operation when loaded to 'N' demand for the engine generator set.

Cummins heavy-duty engine - Rugged 4-cycle industrial diesel delivers reliable power, low emissions and fast response to load changes.

Permanent Magnet Generator (PMG) - Offers enhanced motor starting and fault clearing short circuit capability.

Alternator - Several alternator sizes offer selectable motor starting capability with low reactance 2/3 pitch windings; low waveform distortion with non-linear loads, fault clearing short-circuits capability, and class F or H insulation.

Control system - Standard PowerCommand® electronic control provides total system integration including remote start/stop, precise frequency and voltage regulation, alarm and status message display, AmpSentryTM protection, output metering, auto-shutdown.

Cooling system - Standard integral setmounted radiator system, designed and tested for rated ambient temperatures, simplifies facility design requirements for rejected heat.

Enclosures - Optional weather-protective and sound-attenuated enclosures are available.

Warranty and service - Backed by a comprehensive warranty and worldwide distributor network.

Specifications

Design: 4 cycle, V-block, turbocharged and after-cooled

Bore: 158.8 mm (6.25 in.)

Stroke: 158.8 mm (6.25 in.)

Displacement: 50 L (3067 in3)

Cylinder block engine: Sixteen-cylinder vee formation, direct injection, four-cycle diesel

Battery capacity: 1800 amps at ambient temperature 32 ºF (0 °C)

Battery charging alternator: 55 amps

Starting voltage: 24 volts, negative ground

Fuel system: Direct injection

Fuel filter: Dual spin on paper element fuel filters with standard water separator

Air cleaner type: Dry replaceable element

Lube oil filter type(s): Spin-on paper element full flow and bypass lube oil filters

Standard cooling system: 104 ºF (40 ºC) ambient radiator

generator model
Spec Sheet
Hz
Data Center Continuous kW / kVA
C1250 D6
60
1120 / 1400
C1400 D5
50
1000 / 1250
C1500 D6
60
1286 / 1608
C1675 D5
50
1120 / 1400
C1675 D5A
50
1200 / 1500