6CTA8.3 for Commercial Industrial

Frequency

50, 60 Hz

Rated for kW kVA
Prime 128 - 170 160 - 213
Standby 140 - 185 175 - 231
Continuous 128 - 138 160 - 173

Certification

EPA Tier 1

Product Availability

Africa Middle East, Asia Pacific, Europe, India, Latin America, North America

Applications

Commercial Industrial
6cta8.3 generator
Specifications
  • Cummins® heavy-duty engine - Rugged 4-cycle, industrial diesel delivers reliable power, low emissions and fast response to load changes.
  • Alternator - Several alternator sizes offer selectable motor starting capability with low reactance 2/3 pitch windings, low waveform distortion with non-linear loads and fault clearing short-circuit capability.
  • Control system - The PowerCommand® electronic control is standard equipment and provides total genset system integration including automatic remote starting/stopping, precise frequency and voltage regulation, alarm and status message display, AmpSentry™ protection, output metering, auto-shutdown at fault detection and NFPA 110 Level 1 compliance.
  • Cooling system - Standard integral set-mounted radiator system, designed and tested for rated ambient temperatures, simplifies facility design requirements for rejected heat.
  • Enclosures - Optional weather protective and sound attenuated enclosures are available.
  • Fuel tanks - Dual wall sub-base fuel tanks and in-skid day tanks are also offered.
  • NFPA - The genset accepts full rated load in a single step in accordance with NFPA 110 for Level 1 systems.
  • Warranty
generator model
Spec Sheet
Hz
Prime kW / kVA
Standby kW / kVA
Continuous kW / kVA
fuel type
Availability
engine model
rating
cert
60
165 / 206
170 / 212
Diesel
EPA Tier 1
C175 D5
50
128 / 160
140 / 175
Diesel
C180 D5
50
131 / 164
144 / 180
Diesel
EPA Tier 1
60
170 / 213
185 / 231
Diesel
EPA Tier 1
C200 D5
50
145 / 181
160 / 200
Diesel
C200 D5
50
145 / 182
160 / 200
Diesel
EPA Tier 1
60
165 / 206
170 / 213
128 / 160
Diesel
Africa Middle East, Asia Pacific, Europe, India, Latin America, North America
6CTA8.3-G2
Continuous, Prime, Standby
E.U., mobile application, E.U., stationary application, EPA, nonroad (portable) application, EPA, stationary emergency application, EPA, stationary non-emergency application
60
170 / 213
185 / 231
138 / 173
Diesel
Africa Middle East, Asia Pacific, Europe, India, Latin America, North America
6CTA8.3-G2
Continuous, Prime, Standby
E.U., mobile application, E.U., stationary application, EPA, nonroad (portable) application, EPA, stationary emergency application, EPA, stationary non-emergency application


To access our complete brochure library, click here.
Generator Models

Frequency (Hz)

60

Fuel Type

Diesel

Prime

165 kW

206 kVA

Standby

170 kW

213 kVA

Frequency (Hz)

60

Fuel Type

Diesel

Prime

170 kW

213 kVA

Standby

185 kW

231 kVA

Redirecting to
cummins.com

The information you are looking for is on
cummins.com

We are launching that site for you now.